Rooftop Fan Features:

Ultra-light corrosion resistant FRP dome
The dome made of corrosion resistant FRP material is ideal for protecting the ventilation fan from wind and rain that it is exposed to on the rooftop. The dome is also very light and durable, and can withstand strong wind.

Low noise fan shape
Suiden rooftop ventilation fans are designed with bell mouthed shape to prevent them from producing "BB" noise due to vibration of the fan air inlet mouth.

Rain proof
The fan body utilizes outwards edges, blocking any rainwater brought in by the wind that is not blocked by the dome.

Rooftop Fan Applications:

Where?
Suiden rooftop ventilation fans are suitable for ventilation of large facilities, for exampel:
- Stable ventilation
- Warehouse ventilation
- Factory ventilation etc.

 

standard rooftop fans

Model SRF-R40F SRF-R50F SRF-R60F SRF-R75F SRF-R90F
Power supply 3ph-200V
Fan blade Diameter 400mm 500mm 600mm 735mm 890mm
Qty. 4 Fan blades
Motor Nominal output 200W 400W 750W 1500W 2200W
Poles 4P 6P
Rated current (A) 1.1/1.2A 2.2/2.5A 4.0/4.2A 7.0/7.8A 9.5/10.0A
Weight 27.0kg 39.5kg 59.5kg 89.5kg 133.0kg

Frequency

50 60 50 60 50 60 50 60 50 60

Noise level

(dB)

Air intake port (1.5m) 76 79 69 74 73 77 80 81 84 88
Air exhaust port (1.5m) 65 68 61 64 67 69 71 74 75 80
Air volume (m³/min) at various static pressure* 0Pa 62 69 110 121 154 178 280 310 420 480
20Pa 55 65 103 107 145 167 260 284 392 455
40Pa 50 62 93 100 137 160 245 270 377 441
60Pa 43 57 67 93 129 151 225 255 372 431
80Pa 37 52 52 85 120 143 205 245 367 421
100Pa 30 45 40 73 110 133 186 235 343 411
120Pa 23 38 29 56 99 122 166 225 333 402

* The static pressure is shown in Pascal. 1Pa = 0.10197mmAq.

 